Skip to content
Roxon

Solves: Generators running at low load on construction sites and camps

Roxon BESS 50–150 kW

The Roxon BESS 50, 90 and 150 kW (RS50, RS90, RS150) are skid-mounted LFP storage systems of 102.4, 122.8 and 204.8 kWh, with a 415 V three-phase output. They integrate a 45 kW solar charger with 3 MPPTs, 40 kW grid charging, a static transfer switch under 30 ms and automatic generator control.

50 / 90 / 150 kW102–205 kWh415 VLFPIP54

Ask about this unit View specifications

Roxon BESS 50–150 kW

Illustrative image

Skid-mounted Roxon BESS powering a construction site

Application · Industry and remote operations

Energy for operating away from the grid.

A generator sized for peak demand spends much of its time at low load, especially at night. During those hours it burns fuel and adds maintenance to supply small loads, and hauling the fuel adds cost and logistics.

Used in: Industry and remote operations · Electric mobility

Documentation and warranty

View the application →
01Why this unit
  1. 01

    Overload up to 150 %

    110–120 % for 10 min, 120–130 % for 1 min and 130–150 % for 200 ms.

  2. 02

    45 kW solar charger

    3 MPPTs from 200 to 750 V for fixed or deployable panels.

  3. 03

    Switchover in under 30 ms

    100 kVA static transfer switch between grid and island mode.

  4. 04

    Climate-controlled and IP54

    Two air conditioning units per skid; operates from −20 to 50 °C.

02Models and specifications

3 models: RS50, RS90, RS150. Data from the datasheet, updated October 28, 2026.

Parameter RS50RS90RS150
General
Chemistry Lithium iron phosphate (LFP)
Form factor Steel skid with forklift pockets, lifting and towing points
AC output
Rated power 50 kW90 kW150 kW
Max. apparent power 63 kVA112 kVA188 kVA
Max. active power 63 kW112 kW188 kW
Rated voltage 3P4W + PE, 415 V AC
Frequency 50 Hz
Power factor 0.8–1 inductive or capacitive
Overload 110–120 %: 10 min; 120–130 %: 1 min; 130–150 %: 200 ms
Battery
Rated energy 102.4 kWh122.8 kWh204.8 kWh
Battery modules 202440
Rated capacity 100 Ah
Rated voltage 512 V410 V410 V
Operating voltage range 448–576 V358–461 V358–461 V
Recommended charge and discharge current 50 A
Solar input
PV charger power 45 kW
Max. PV voltage 830 V
MPPT voltage range 200–750 (430–750 at full load) V
Number of MPPTs 3
Max. current per MPPT 35 / 35 / 35 A
Start-up voltage 250 V
AC input (charging)
AC charging power 40 kW
Input voltage 415 V (323–456 V AC), three-phase + PE
Input frequency 45–65 Hz
System
Static transfer switch (STS) 100 kVA, grid / island switchover < 30 ms
Climate control 2 units, 0.6 kW cooling each2 units, 1.5 kW cooling each2 units, 5 kW cooling each
Control Automatic generator start and stop (ATS), integrated BMS
Scalability Multiple units daisy-chained
Environment
Ingress protection IP54
Operating temperature −20 to 50 °C
Noise level 75 dBA
Physical
Dimensions (length × width × height) 1,900 × 1,460 × 2,250 mm2,438 × 1,965 × 2,100 mm2,991 × 2,280 × 2,491 mm
Weight 2,400 kg3,600 kg6,100 kg

Send us the load, the hours of autonomy you need and the sources you have. We’ll send back a configuration with equipment and datasheets.

Ask about this unit

Questions about the Roxon BESS 50–150 kW

What is the difference between the BESS 50, 90 and 150 kW?

Power and energy: 50 kW with 102.4 kWh, 90 kW with 122.8 kWh and 150 kW with 204.8 kWh. All three share a 45 kW solar charger, 40 kW grid charging, a 415 V three-phase output and IP54 protection.

Can the Roxon BESS work with a generator?

Yes. It includes automatic generator start and stop (ATS) and an integrated BMS. It operates off-grid, with a generator, with panels or with the grid, and several units can be connected in a chain.

How is the Roxon BESS transported?

On a steel skid with forklift pockets and lifting and towing points. It weighs 2,400 kg for the 50 kW, 3,600 kg for the 90 kW and 6,100 kg for the 150 kW.

+Other products
  1. Roxon Mobile 15 kW Pumps and loads that change location
  2. Roxon BESS Pro 270–540 kW Large loads that currently depend on a generator
  3. Roxon BESS Gen 10–30 kW Sites with no grid and no generator of their own
  4. Roxon Hybrid 6.2 kW Power outages in homes and shops